Gym Door Question
We are wanting to put access control on a Gym we are building and are being told that it would violate fire code. Could someone please help understand what is wrong with our desired setup? We were told...
View Article11" wide firewall -what size rated door jamb?
i have a ul u336 area separation firewall with a width of 11-1/2" and trying to find a detail for the door jamb. should the jamb be the fill 11"+ wide or can it be a standard rated jamb fire caulked...
View ArticleUL 10c 1 hr label on mag locks, or only UL label with no time listed
Door inspector called out UL 10c 1 hr label on mag locks installed on 90 min opening protectives. Also called out another model mag lock that has UL label with no time listed on a 45 min opening. What...
View ArticleLori made the big time!!!
https://linkprotect.cudasvc.com/url?a=https://www.iccsafe.org/building-safety-journal/bsj-perspectives/icc-members-shaping-the-safety-of-the-world-around-us-lori-greene/&c=E,1,3E4sxXCZBlNskoiqDlY5O...
View ArticleSlammer doors
Do "slammers" need to be self-latching? 2018 IBC 3006.3 #3 has the slammer option, but don't indicate or reference any section that would require a latching mechanism or hardware requirements, other...
View ArticleChurch Door
We have enclosed the front porch on our Church building and are ready to install a door. The arched door opening is 8' high by 6' wide. The door will be two 3'x8' arched panels made of Cyprus. There is...
View ArticleFire Hoses
Hello and Happy New Year! I have a rule against making New Year's resolutions, but I am going to make an effort to proactively share more info here rather than just responding to questions as they come...
View Articledoor closers don't latch
I have an ALF that has a problem with the fire doors and closers. This has been an ongoing problem since the building was new in about 1997. The initial problems: 1. The doors did not latch, the...
View ArticleFreight Elevator Lobby Issue
So to build off my Fire Door question. I have a Freight Elevator Lobby the customer wants to control access through from the Lobby into the space. The issue is egress out of that lobby to get to the...
View ArticleFire Door Signage
For all of the AHJs out there...I would like to know if you would approve signage on fire doors that meets the 2022 edition of NFPA 80, in jurisdictions where that edition has not yet been adopted. In...
View ArticleHelp! Minimum projection Panic for 48" x 1 3/4" door
CFC 2019 requires 44" min. clr width at 90 degrees, face 0f hardware to face of door, full height for I-2 hospital even with layback hinge can this be done without inset panic bars? They don't buy ADA...
View ArticleCalifornia MagLocked Showroom Door
My building is an Auto Dealership in Anaheim, California. The showroom has 5 glass door exits that are all potential means of egress from the building. The showroom doors are always open/unlocked...
View ArticleFire Door Two-Point Latching Options and Minimum Latch Points from Door to Frame
First part of this question is the general question: What is the minimum number of latch points that must be between the door and frame (excludes door-to-door latch points)? My understanding from a...
View ArticleFire Doors
A GC I am working with informed me that any fire rated door had to positively latch. I was aware that stairwell doors had to stay positively latched. But if a door is part of a rated fire wall, and has...
View ArticleType of controlled egress
I have a facility that requires the use of a type of sally port for pairs of doors. It is a manufacturing facility (F1) that requires operational control over hygiene and sterility, so an occupant must...
View Articleswinging doors kitchens
We are a residential apartment complex (high rise) with a restaurant/kitchen area on the first floor. The kitchen staff wants to replace one of the swinging doors with an automatic door to allow for...
View ArticleNOVEL DOOR HARDWARE
This is my first post. I'm a Canberra Australia architect with a door hardware obsession. I'm sometimes commisioned to design solutions to interesting problems. This push lock floor bolt was fitted...
View ArticlePanic Escape
Sometimes the person doing the door documentation is confronted with a dilemma. Electrical/security documentation will often compromise personal safety of those who need to escape at any time for any...
View ArticleReinforced (non-FEMA Tornado) room door hardware
We designed a 10 stall bathroom as a tornado shelter. Extra studs, stand alone structure, cmu drystack in the walls, extra sheathing, etc. Our issue is the door. The door itself is metal reinforced,...